Wiring Separation
All high voltage and non-power limited wiring must be kept separate from power limited wiring.
A separation of at least 1/4 inch must be maintained with high voltage and non-power limited
wiring running in separate conduit openings from power limited wiring.
AC input
NAC-2
NAC-1
P2
Dialer
Relay-1
Relay-2
7 Optional field wire knock-outs
Power limited
N
on
po
we
r
l
i
mi
te
d
Relay-3
Relay-4
34