8700 SLC Manual Pull Stations
Manual Station, Single Action
Manual Station, Double Action
Metal Manual Station, Single Action
8700 SLC Detectors
Thermal Detector, Fixed or Fixed/Rate of Rise
8700 SLC Modules
Single input interface module
Dual input interface module
Single input interface module with relay
Mini single input interface module
Intelligent control point
8700 SLC Bases
8700 SLC Accessories
Intelligent Remote Lamp, Ceiling mount
Intelligent Remote Lamp, Wall mount
Remote Lamp, Ceiling mount
Air Duct Housing with Relay
Notes:
1. Siemens SLC devices, detectors and modules, up to a maximum of 50 addresses may be used.
2. For specific wiring and installation information, read the instructions provided with each device.
3. If more than one HCP is used on a SLC device loop, the loop must be wired Class A or the riser conductors must be installed in
accordance with the Survivability From Attack By Fire requirements in the National Fire Alarm Code, NFPA 72. If wired Class A, at least
one HLIM loop isolator must be installed between each HCP and between the panel and the first and last HCP. See the HLIM installation
instructions for the maximum number of isolators allowed per loop and other wiring instructions.
FD182UL
53