APPENDIX-F: TESTING/MAINTENANCE
If the system is connected to the fire department, etc., or actuates an internal system, disarm
the appropriate outputs before servicing to prevent actuation. Notify the fire department and
personnel at your facility that a System test is being performed so that any alarm sounding can
be ignored during the test. Notify the fire department before resetting the system.
Inspection, Testing, and Maintenance of the fire alarm system should be performed in
accordance with NFPA 72, The National Fire Alarm Code and all applicable local codes.
BATTERY MAINTENANCE
Perform the following tests at the recommended interval. Replace the battery set every four
years or if any of the test criteria are not met.
Initiation / Reacceptance
1. Charger TestWith the batteries fully charged and connected to the charger, measure the
voltage across the battery set. It must read 27.3V ± 0.3V.
2. Discharge TestWith full system alarm load, the voltage on a fully charged battery must
not fall below 20.4V after 30 minutes.
3. Load Voltage TestWith full system alarm load, the voltage on a fully charged battery must
not fall below 24.6V after one minute.
Testing Interval
1. SemiannuallyPerform the Load Voltage Test.
2. AnnuallyPerform the Charger Test and Discharge Test.
58

Table of Contents

Other manuals for Siemens FC901-U3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FC901-U3 and is the answer not in the manual?

Siemens FC901-U3 Specifications

General IconGeneral
BrandSiemens
ModelFC901-U3
CategoryControl Panel
LanguageEnglish

Related product manuals