Application and properties   
1.4 Requirements for use 
  IE/PB LINK PN IO 
20  Operating Instructions, 11/2017, C79000-G8976-C393-02 
Below you will find the STEP 7 products required to configure the LINK. If both STEP 7 V5.x 
as well as STEP 7 Basic / Professional are named, one of the two products can be used as 
an alternative. 
 
STEP 7 V5.3 SP1  LINK with article number 6GK1 411-5AB00 
The functionality of firmware version V1.0 can be used. 
•  STEP 7 V5.3 + SP2 + Hotfix 1 + HSP 1007 
•  STEP 7 Basic / Professional V11 
LINK with article number 6GK1 411-5AB00 
The functionality of firmware version V2.x can be used. 
•  STEP 7 V5.5 + SP4 + Hotfix 11 + HSP 1101 
•  STEP 7 Basic / Professional V14 + Update 
1 + Support package 0192 
LINK with article number 6GK1 411-5AB10 
The functionality of firmware version V3.0 can be used. 
Downloading the support package / HSP from the Internet 
You will find the HSP or support package on the following Internet pages of Siemens 
Industry Support. 
●  STEP 7 V5.x 
Link: (https://support.industry.siemens.com/cs/ww/en/view/23183356) 
●  STEP 7 Basic / Professional 
Link: (https://support.industry.siemens.com/cs/ww/en/ps/14667/dl) 
Installation of Hardware Support Packages 
●  STEP 7 V5.x 
Install the HSP in STEP 7 / HW Config with the "Options" > "Install Hardware Updates" 
menu command. 
You will find information in the online help: Keyword "HSP" or "Hardware update"). 
After installing an HSP, you need to close and restart STEP 7. 
●  STEP 7 Basic / Professional 
Install the support package in STEP 7 from the file system of the engineering station 
using the menu command "Options" > "Support packages". 
The information system of STEP 7 will provide you with information: Keyword "Support 
packages". 
Version V4.2.1 is required for configuration with the PST. 
You can download the current version from the pages of Siemens Industry Support: 
Link: (https://support.industry.siemens.com/cs/ww/en/view/19440762)