EasyManuals Logo

Siemens LMV3 series User Manual

Siemens LMV3 series
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #152 background imageLoading...
Page #152 background image
Error
Code
Diag.
Code
Meaning for the LMV3 System Corrective Action
Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
117 0 Lifetime exceeded - operation no longer allowed Replace the LMV3.
120 0 Interrupt limitation fuel meter input
The LMV3 has detected too many disturbance pulses at the fuel meter
input. Reduce electrical noise and reset the fault.
121 Any # Internal error EEPROM access
122 Any # Internal error EEPROM access
123 Any # Internal error EEPROM access
124 Any # Internal error EEPROM access
125 Any # Internal error EEPROM read access
126 Any # Internal error EEPROM write access
127 Any # Internal error EEPROM access
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. Restore the parameter set if possible. If the
fault occurs continuously, replace the LMV3.
128 0 Internal error EEPROM access - synchronization during initialization If the fault occurs continuously, replace the LMV3.
129 Any # Internal error EEPROM access - command synchronization
130 Any # Internal error EEPROM access - timeout
131 Any # Internal error EEPROM access - page on abort
132 Any # Internal error EEPROM register initialization If the fault occurs continuously, replace the LMV3.
133 Any # Internal error EEPROM access - request synchronization
134 Any # Internal error EEPROM access - request synchronization
135 Any # Internal error EEPROM access - request synchronization
Any # Restore
1 Restore started - for further diagnostic codes, refer to error code 137
136
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. If the fault occurs continuously, replace the
LMV3.
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. If the fault occurs continuously, replace the
LMV3.
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. If the fault occurs continuously, replace the
LMV3.
No fault: A restore was started via parameter 050. New LMV3s require a
reset after a restore. Reset the LMV3.
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. Restore the parameter set if possible. If the
fault occurs continuously, replace the LMV3.
Section 6 Page 18 SCC Inc.

Table of Contents

Other manuals for Siemens LMV3 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV3 series and is the answer not in the manual?

Siemens LMV3 series Specifications

General IconGeneral
BrandSiemens
ModelLMV3 series
CategoryControl Unit
LanguageEnglish

Related product manuals