Meaning for the LMV3 System Corrective Action
Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
117 0 Lifetime exceeded - operation no longer allowed Replace the LMV3.
120 0 Interrupt limitation fuel meter input
The LMV3 has detected too many disturbance pulses at the fuel meter
input. Reduce electrical noise and reset the fault.
121 Any # Internal error EEPROM access
122 Any # Internal error EEPROM access
123 Any # Internal error EEPROM access
124 Any # Internal error EEPROM access
125 Any # Internal error EEPROM read access
126 Any # Internal error EEPROM write access
127 Any # Internal error EEPROM access
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. Restore the parameter set if possible. If the
fault occurs continuously, replace the LMV3.
128 0 Internal error EEPROM access - synchronization during initialization If the fault occurs continuously, replace the LMV3.
129 Any # Internal error EEPROM access - command synchronization
130 Any # Internal error EEPROM access - timeout
131 Any # Internal error EEPROM access - page on abort
132 Any # Internal error EEPROM register initialization If the fault occurs continuously, replace the LMV3.
133 Any # Internal error EEPROM access - request synchronization
134 Any # Internal error EEPROM access - request synchronization
135 Any # Internal error EEPROM access - request synchronization
Any # Restore
1 Restore started - for further diagnostic codes, refer to error code 137
136
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. If the fault occurs continuously, replace the
LMV3.
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. If the fault occurs continuously, replace the
LMV3.
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. If the fault occurs continuously, replace the
LMV3.
No fault: A restore was started via parameter 050. New LMV3s require a
reset after a restore. Reset the LMV3.
Reset the fault and check to make sure the last parameter that was viewed
/ changed is set properly. Restore the parameter set if possible. If the
fault occurs continuously, replace the LMV3.
Section 6 Page 18 SCC Inc.