EasyManuals Logo

Siemens LMV3 series User Manual

Siemens LMV3 series
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
Error
Code
Diag.
Code
Meaning for the LMV3 System Corrective Action
Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
Any # Timeout building automation interface
1 Modbus timeout
2 Reserved
Any # TUV test
A fault occurred during the TUV test. See diagnostic codes for more
information.
1 (-1) Invalid phase
The TUV test can only be started in phase 60 (operation). Reset the fault.
When the LMV3 reaches phase 60, attempt to start the TUV test again.
2 (-2) TUV test default output too low
The TUV test default output (parameter 133/134) cannot be set lower than
the lower load limit (parameter 545/565). Either increase the TUV test
default output or decrease the lower load limit, then reset the fault.
3 (-3) TUV test default output too high
The TUV test default output (parameter 133/134) cannot be set higher
than the upper load limit (parameter 546/566). Either decrease the TUV
test default output or increase the upper load limit, then reset the fault.
4 (-4) Manual interruption No fault: The TUV test was aborted manually by the user.
5 (-5) TUV test timeout
There was no loss of flame after shutdown of the fuel valves. Check for
extraneous light or a faulty flame scanner, then reset the fault and start
the TUV test again.
Any # Trim function: Invalid analog value
1 Start prevention
2 Warning (trim function temporarily disabled)
Any # Trim function: Invalid curve setting of VSD / PWM blower
The following equations set the limits on the curve settings for the VSD /
PWM blower.
Fuel 0: Parameter 669:00 + parameter 547 ≤ curve point ≤ parameter
669:01 - parameter 548
Fuel 1: Parameter 669:00 + parameter 567 ≤ curve point ≤ parameter
669:01 - parameter 568
1-9 Minimum value VSD curve invalid
A VSD curve point is below the permissible minimum value (diagnostic
code = point number, example: 1 = point P1)
21-29 Maximum value VSD curve invalid
A VSD curve point is above the permissible maximum value (diagnostic
code = point number, example: 21 = point P1)
41-49 Fuel 1: Minimum value VSD curve invalid
Fuel 1: A VSD curve point is below the permissible minimum value
(diagnostic code = point number, example: 41 = point P1)
61-69 Fuel 1: Maximum value VSD curve invalid
Fuel 1: A VSD curve point is above the permissible maximum value
(diagnostic code = point number, example: 61 = point P1)
155
146
150
154
Modbus communication has been interrupted for longer than the setting
of parameter 142. Re-establish communication, then reset the fault.
An invalid 4-20 mA signal was detected on input X64. Check the wiring to
terminal X64. Check the value of parameter 916. A value under -16%
indicates <4 mA is being detected, while a value over 26% indicates >20
mA is being detected.
Section 6 Page 20 SCC Inc.

Table of Contents

Other manuals for Siemens LMV3 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV3 series and is the answer not in the manual?

Siemens LMV3 series Specifications

General IconGeneral
BrandSiemens
ModelLMV3 series
CategoryControl Unit
LanguageEnglish

Related product manuals