Meaning for the LMV3 System Corrective Action
Note: Diagnostic codes are additive. If a diagnostic code appears that is not on this list, it is a combination of multiple diagnostic codes.
206 0 Inadmissible combination of units (LMV3 / AZL23)
Reset the LMV3. If the fault occurs continuously, replace the LMV3 and /
or AZL23.
Any # Version compatibility LMV3 / AZL23
0 LMV3 version is too old
1 AZL23 version is too old
208 Any # Internal error
209 Any # Internal error
210 0 Selected operation mode is not released for the LMV3 Select a different operation mode via parameter 201/301.
240 Any # Internal error If the fault occurs continuously, replace the LMV3.
Any # Invalid parameterization Make a valid selection of parameter 277/377, then reset the fault.
0 Invalid setting of parameter 277 Set parameter 277 to a valid value.
1 Invalid setting of parameter 377 Set parameter 377 to a valid value.
245 Any # Internal error
250 Any # Internal error
242
If the fault occurs continuously, replace the LMV3.
If the fault occurs continuously, replace the LMV3.
Replace the unit called out in the diagnostic code. Be sure that the new
unit has up-to-date software.
207
Section 6 Page 23 SCC Inc.