EasyManuals Logo

Siemens LMV3 series User Manual

Siemens LMV3 series
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #168 background imageLoading...
Page #168 background image
Technical Instructions LMV Series
Document No. LV3-1000
Section 7 Page 8 SCC Inc.
Function
Address
dec/hex
Number
of words
Data designation
Access
Data
format
Data type /
coding
Range
R
03/04
W 06/16
8
5/55h
1
Preselected output in the event
communication with BACS breaks
down (fuel 1)
R/W*
EEPROM
U16
Fire rate
Modulating:
0…100%
Multistage:
1001…1003
Invalid:
32767
03/04
98
/62h
8
Burner control
type reference
(ASN)
R
U8[16]
String
03/04
106
/6Ah
1
Burner control parameter set code
R
U16
03/04
107
/6Bh
1
Burner control parameter set
version
R
U16
03/04
108
/6Ch
3
Burner control identification date
R
U16[3]
Data
03/04
111
/6Fh
1
Burner control identification
number
R
U16
03/04
113
/71h
1
Software version burner control
R
U16
Hexadecimal
03/04
115
/73h
8
Burner identification
R
U8[16]
String
03/04
123
/7Bh
1
Minimum output fuel 0
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
124/7Ch
1
Maximum output fuel 0
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
12
5/7Dh
1
Minimum output fuel 1
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
12
6/7Eh
1
Maximum
output fuel 1
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
127/7Fh
1
Operation mode of burner fuel 0
R
U16
1…27
03/04
128/80h
1
Operation mode of burner fuel 1
R
U16
1…27
03/04
129/81h
2
Switching cycles
Revert to pilot
R
S32
0…9999999
03/04
140/8Ch
1
Operation mode of burner
fuel 0
R
U16
1…29
03/04
141/8Dh
1
Operation mode of burner fuel 1
R
U16
1…29
03/04
142/8Eh
2
Switching cycles
Revert to pilot
R
S32
0…9999999
03/04
144/90
1
Lower range limit trim function fuel
0
R
S16
Percent
0…
-
15%
03/04
145/91
1
Upper range limit trim function fuel
0
R
S16
Percent
0…25%
03/04
146/92
1
Lower range limit trim function fuel
1
R
S16
Percent
0…
-
15%
03/04
147/93
1
Upper range limit trim function fuel
1
R
S16
Percent
0…25%
03/04
148/94
1
Input value analog input trim
function
R
S16
Percent
-
15…+25%

Table of Contents

Other manuals for Siemens LMV3 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LMV3 series and is the answer not in the manual?

Siemens LMV3 series Specifications

General IconGeneral
BrandSiemens
ModelLMV3 series
CategoryControl Unit
LanguageEnglish

Related product manuals