Technical Instructions LMV Series
Document No. LV3-1000
Section 7 Page 8 SCC Inc.
Function
Address
dec/hex
Number
of words
Data designation
Access
Data
format
Data type /
coding
Range
R
03/04
W 06/16
8
5/55h
1
Preselected output in the event
communication with BACS breaks
down (fuel 1)
R/W*
EEPROM
U16
Fire rate
Modulating:
0…100%
Multistage:
1001…1003
Invalid:
32767
03/04
98
/62h
8
Burner control
type reference
(ASN)
R
U8[16]
String
03/04
106
/6Ah
1
Burner control parameter set code
R
U16
03/04
107
/6Bh
1
Burner control parameter set
version
R
U16
03/04
108
/6Ch
3
Burner control identification date
R
U16[3]
Data
03/04
111
/6Fh
1
Burner control identification
number
R
U16
03/04
113
/71h
1
Software version burner control
R
U16
Hexadecimal
03/04
115
/73h
8
Burner identification
R
U8[16]
String
03/04
123
/7Bh
1
Minimum output fuel 0
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
124/7Ch
1
Maximum output fuel 0
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
12
5/7Dh
1
Minimum output fuel 1
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
12
6/7Eh
1
Maximum
output fuel 1
R
U16
Fire rate
limit
20…100%
1001…1003
Invalid:
32767
03/04
127/7Fh
1
Operation mode of burner fuel 0
R
U16
1…27
03/04
128/80h
1
Operation mode of burner fuel 1
R
U16
1…27
03/04
129/81h
2
Switching cycles
Revert to pilot
R
S32
0…9999999
03/04
140/8Ch
1
Operation mode of burner
fuel 0
R
U16
1…29
03/04
141/8Dh
1
Operation mode of burner fuel 1
R
U16
1…29
03/04
142/8Eh
2
Switching cycles
Revert to pilot
R
S32
0…9999999
03/04
144/90
1
Lower range limit trim function fuel
0
R
S16
Percent
0…
-
15%
03/04
145/91
1
Upper range limit trim function fuel
0
R
S16
Percent
0…25%
03/04
146/92
1
Lower range limit trim function fuel
1
R
S16
Percent
0…
-
15%
03/04
147/93
1
Upper range limit trim function fuel
1
R
S16
Percent
0…25%
03/04
148/94
1
Input value analog input trim
function
R
S16
Percent
-
15…+25%

Table of Contents