LMVSeriesTechnicalInstructions
DocumentNo.LV31000
SCCInc. Page5 Section2
LMV3Terminals
Terminal Type Function Parameter Rating
X503.1 FixedInput Burnerswitch Notconfigurable
1.5mA,
120VAC
X503.2
Programmable
Input
LMV37‐Decreasefirerate/
stage3oil‐or‐
Reverttopilot
LMV36‐Fuel0select
191‐Reverttopilot
205‐Stagedconfig
942‐Activeloadsource
X503.3
LMV37‐Increasefirerate/
stage2oil
LMV36‐Fuel1select
205‐Stagedconfig
942‐Activeloadsource
X503.4 Line Line,fused
Notconfigurable
500mA,
120VAC
X603.1 PE ProtectiveEarthground
N/A
X603.2 Neutral Neutral
X603.3 FixedOutput
Outsidemainsafetyvalve
Typical:Atomizingair
compressororgasbooster
2A,120VAC
X701.1 PE ProtectiveEarthground
N/A
X701.2 Neutral Neutral
X701.3
Programmable
Output
MainfuelvalveV2
(downstream)
or‐
stage2oilvalve
191‐Reverttopilot
231/271/331/371‐
Safetytime2
232/272/332/372‐Interval
2
241/341‐Valveproving
1.6A,
120VAC
X702.1 PE ProtectiveEarthground
Notconfigurable N/A
X702.2 Neutral Neutral
X702.3
Programmable
Output
Gaspilotvalve
or‐
stage3oilvalve
191‐Reverttopilot
227/267/327/367‐
Safetytime1
230/270/330/370‐Interval
1
231/271/331/371‐
Safetytime2
1.6A,
120VAC