TechnicalInstructions LMVSeries
DocumentNo.LV3‐1000
Section2 Page6 SCCInc.
LMV3Terminals
Terminal Type Function Parameter Rating
X8‐02.1
Programmable
Output
MainfuelvalveV1(upstream)
‐or‐
stage1oilvalve
191‐Reverttopilot
231/271/331/371‐
Safetytime2
232/272/332/372‐Interval
2
241/341‐Valveproving
1.6A,
120VAC
X8‐02.2 TiePoint Useasatiepoint(EUuseonly)
Notconfigurable N/A
X8‐02.3 Neutral Neutral
X8‐02.4 PE ProtectiveEarthground
X8‐04.1 FixedInput
Remoteresetandmanual
lockout
Notconfigurable
1.5mA,
120VAC
X8‐04.2 FixedOutput Mainvalveindicator
N/A
X9‐04.1 PE ProtectiveEarthground
X9‐04.2
Programmable
Input
Valveprovingpressureswitch
‐or‐
Lowoilpressureswitch
217‐Maxtimehomerun
241/341‐Valveproving
242/342‐VPevacuation
time
243/343‐VPupstreamtest
244/344‐VPfilltime
245/345‐VPdownstream
test
276/376‐LowoilPS
286‐StartreleaseHO
287‐MaxtimeSRHO
1.5mA,
120VAC
X9‐04.3 Line Line,fused
Notconfigurable
500mA,
120VAC
X10‐05.1 PE ProtectiveEarthground N/A
X10‐05.2
Programmable
Input
Ionizationprobesignal(flame
rod)
186/187‐FFRT
197‐Flamesensitivity
221/261/321/361‐
Flamedetectorselect
1mA
X10‐05.3 QRBsignal(EUonly) 8VDC
X10‐05.4 Ground QRBground(EUonly)
Notconfigurable
N/A
X10‐05.5 Line Line,fused
500mA,
120VAC
X10‐06.1
Programmable
Input
QRAsignal
186/187‐FFRT
197‐Flamesensitivity
221/261/321/361‐
Flamedetectorselect
Max600µA
X10‐06.2 Ground QRAground Notconfigurable N/A