LMVSeriesTechnicalInstructions
DocumentNo.LV3‐1000
SCCInc. Page7 Section2
LMV3Terminals
Terminal Type Function Parameter Rating
X53.1
Airactuator
Power
Notconfigurable N/A
X53.2 Ground
X53.3 OutputchannelA
X53.4 OutputchannelB
X53.5 InputchannelA
X53.6 InputchannelB
X54.1
Fuelactuator
Power
X54.2 Ground
X54.3 OutputchannelA
X54.4 OutputchannelB
X54.5 InputchannelA
X54.6 InputchannelB
X56 BCIPort
AZL23‐or‐OCI410PC
cable
X64.1
Programmable
Input
4‐20mA(+)forload
control‐or‐VSDspeed
shift
204‐Invalidanalogin
530‐VSDspeedshift
550/570‐Shiftdelay
3‐20mA,460Ω
X64.2
4‐20mA(‐)forload
control‐or‐VSDspeed
shift
X64.3
Programmable
Output
PWMspeedcontrol
signal
(toblower)
542‐VSDactivation
641‐VSDstandardization
643‐Typespeedfeedback
644‐Feedbackpulse/rev
662‐VSDneutralzone
663‐VSDnearzone
1964Hzcarrier
frequency
X64.4
Programmable
Input
PWMspeedfeedback
(fromblower)
14.5‐26VDC,
15‐1400Hz
X64.5 FixedOutput Powersupplyforsensor Notconfigurable N/A