TechnicalInstructions LMVSeries
DocumentNo.LV3‐1000
Section2 Page10SCCInc.
AGM60Terminals
Terminal Type Function Rating
X5‐01.1 PE ProtectiveEarthground N/A
X5‐01.2 Input
Valveprovingpressureswitch‐or‐
lowoilpressureswitch(fuel1)
1.5mA,120VAC
X5‐01.3 Line Line,fused 500mA,120VAC
X5‐02.1 PE ProtectiveEarthground N/A
X5‐02.2 Input
Gastrains:HighgasPS‐or‐POC‐or‐
valveprovingpressureswitch
Oiltrains:HighoilPS‐or‐POC(fuel1)
1.5mA,120VAC
X5‐02.3 Line Line,fused 10mA,120VAC
X6‐02.1 PE ProtectiveEarthground
N/A
X6‐02.2 Neutral Neutral
X6‐02.3
Output
Outsidemainsafetyvalve
Typical:atomizingaircompressororgasbooster
(fuel1)
1.6A,120VAC
X8‐02.1
MainfuelvalveV1
(upstream‐fuel1)
X8‐02.2 TiePoint Useasatiepoint(EUuseonly)
N/AX8‐02.3 Neutral Neutral
X8‐02.4 PE ProtectiveEarthground
X8‐03.1 Output
MainfuelvalveV2
(downstream‐fuel1)
1.6A,120VAC
X8‐03.2 TiePoint Useasatiepoint(EUuseonly)
N/A
X8‐03.3 Neutral Neutral
X8‐03.4
PE ProtectiveEarthground
X9‐04.1
X9‐04.2 Input
Valveprovingpressureswitch‐or‐
lowoilpressureswitch(fuel0)
1.5mA,120VAC
X9‐04.3 Line Line,fused 500mA,120VAC
X22‐02.1 PE ProtectiveEarthground N/A
X22‐02.2 Input
Gastrains:HighgasPS‐or‐POC‐or‐
valveprovingpressureswitch
Oiltrains:HighoilPS‐or‐POC(fuel0)
1.5mA,120VAC
X22‐02.3 Line Line,fused 10mA,120VAC
X24‐04.1 PE ProtectiveEarthground
N/A
X24‐04.2 Neutral Neutral
X24‐04.3
Output
MainfuelvalveV2(downstream‐fuel0)
1.6A,120VAC
X24‐04.4 MainfuelvalveV1(upstream‐fuel0)