AGM60Terminals
Terminal Type Function Rating
X24‐06.1 PE ProtectiveEarthground
N/A
X24‐06.2 Neutral Neutral
X24‐06.3 Output
Outsidemainsafetyvalve
Typical:atomizingaircompressororgas
booster(fuel0)
1.6A,120VAC
X31‐01.1 Input
Fuelselect
De‐energized=fuel0
Energized=fuel1
1.5mA,120VAC
X31‐01.2 PE ProtectiveEarthground
N/A
X31‐01.3 Neutral Neutral
X31‐01.4 Line Line,fused 500mA,120VAC
X31‐02.1
Output
Fuelselectfuel0
Max.10mA
X31‐02.2 Fuelselectfuel1
X32‐01.1
Gastrains:HighgasPS‐or‐POC‐or‐
valveprovingpressureswitch
Oiltrains:HighoilPS‐or‐POC(common)
1.5mA,120VAC
X32‐01.2
Input
MainfuelvalveV1(upstream‐common)
1.6A,120VAC
X32‐01.3 MainfuelvalveV2(downstream‐common)
X32‐01.4 Output
Valveprovingpressureswitch‐or‐
lowoilpressureswitch(common)
1.5mA,120VAC
X32‐01.5 Input
Outsidemainsafetyvalve
Typical:atomizingaircompressororgas
booster(common)
1.6A,120VAC
X32‐02.1 Output
Burnerswitch 1.5mA,120VAC
X32‐02.2 Input
X54 Actuator ConnectcableAGV61.100
N/A
X54a.1
Fuel1‐Fuel
actuator
Power
X54a.2 Ground
X54a.3 OutputchannelA
X54a.4 OutputchannelB
X54a.5 InputchannelA
X54a.6 InputchannelB
X54b.1
Fuel0‐Fuel
actuator
Power
X54b.2 Ground
X54b.3 OutputchannelA
X54b.4 OutputchannelB
X54b.5 InputchannelA
X54b.6 InputchannelB