188/213
Building Technologies Basic documentation LMV37.4... CC1P7546en
HVAC Products 27 Parameter list LMV37.4... 01.12.2009
Par.
Parameter Number of Type Edit Value range Resolution Default Password level
no. elements Min Max setting
281 Oil: Time oil ignition
0 = short preignition (Ph38)
1 = long preignition (with fan) (Ph22)
1 Selection edit 0 1 1
LMV37.400...: 1
LMV37.420...: 0
SO
284 Oil: Postpur
e time
t3
abortion with load controller
(LR)-ON
1 Time edit 1 s 108 min 0.2 s 1 s SO
400 Ratio curves
401
Ratio control curve fuel actuator (only curve settings)
13 Std_s16 edit 0 ° 90 ° 0.1 ° 0 °; 0 °; 15 °; undefined SO
402
Ratio control curve air actuator (only curve settings)
13 Std_s16 edit 0 ° 90 ° 0.1 ° 0 °; 90 °; 45 °; undefined SO
403
Ratio control curve VSD (only curve settings)
13 Std_s16 edit 20% 100% 0.1% 0%; 100%; 50%; unde-
fined
SO