HVAC Products 27 Parameter list LMV37.4... 01.12.2009
Par.
Parameter Number of Type Edit Value range Resolution Default Password level
no. elements Min Max setting
500 Ratio control
501 No-flame positions fuel actuator
Index 0 = no-load position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16 edit 0 ° 90 ° 0.1 ° 0 °; 0 °; 15 ° SO
502 No-flame positions air actuator
Index 0 = no-load position
Index 1 = prepurge position
Index 2 = postpurge position
3 Std_s16 edit 0 ° 90 ° 0.1 ° 0 °; 90 °; 45 ° SO
503 No-flame speeds VSD
Index 0 = no-load speed
Index 1 = prepurge speed
Index 2 = postpurge speed
3 Std_s16 edit 0% 100% 0.1% 0%; 100%; 50% SO
522 Ramp up 1 Std_u8 edit 5 s 20 s 1 s 10 s SO
523 Ramp down 1 Std_u8 edit 5 s 20 s 1 s 10 s SO
542 Activation of VSD / PWM fan
0 = inactive
1 = active
1 Selection edit 0 1 1 0 SO
545 Lower output limit
undefined = 20 %
1 Output edit / clear 20% 100% 0.1% undefined SO (BA)
546 Upper output limit
undefined = 100 %
1 Output edit / clear 20% 100% 0.1% undefined SO (BA)