EasyManua.ls Logo

Siemens MICROMASTER 420 - Digital Output (DOUT); Selection of Frequency Setpoint

Siemens MICROMASTER 420
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Issue 04/04 6 Commissioning
MICROMASTER 420
Compact Operating Manual
17
6.2.4 Digital output (DOUT)
P0731 =...
BI: Function of digital output 1*
Defines source of digital output 1.
P0748 = 0
Invert digital output
Defines high and low states of relay for a
given function.
Common Settings:
52.0 Drive ready 0 Closed
52.1 Drive ready to run 0 Closed
52.2 Drive running 0 Closed
52.3 Drive fault active 0 Closed
52.4 OFF2 active 1 Closed
52.5 OFF3 active 1 Closed
52.6 Switch on inhibit active 0 Closed
52.7 Drive warning active 0 Closed
-1
0
1
Invert DOUTs
0 ... 1
P0748 (0)
CO/BO: State DOUTs
r0747
r0747
Kl.10
Kl.11
.0
DOUT channel
NO
COM
(52:3)
BI: Fct. of DOUT 1
P0731
6.2.5 Selection of frequency setpoint
P1000 =...
Selection of frequency setpoint
0 No main setpoint
1 MOP setpoint
2 Analog setpoint
3 Fixed frequency
4 USS on BOP link
5 USS on COM link
6 CB on COM link
MOP
ADC
FF
USS
BOP link
USS
COM link
CB
COM link
P1000 = 12
P1000 = 12
Sequence control
Additonal
setpoint
Main
setpoint
Setpoint
channel
Motor
control
52.3
0
2