EasyManua.ls Logo

Siemens MICROMASTER 420 - Jog; Ramp-Function Generator (HLG)

Siemens MICROMASTER 420
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6 Commissioning Issue 04/04
MICROMASTER 420
20 Compact Operating Manual
6.2.10 JOG
P1058 =...
JOG frequency right
Frequency in Hz when the motor is being
jogged in the clockwise direction of rotation.
P1059 =...
JOG frequency left
Frequency in Hz when the motor is being
jogged in the counter-clockwise direction of
rotation.
P1060 =...
JOG ramp-up time
Ramp-up time in s from 0 to the maximum
frequency (P1082). The JOG ramp-up is
limited by P1058 or P1059.
P1061 =...
JOG ramp-down time
Ramp-down time in s from the maximum
frequency (P1082) to 0.
P1082
(f
max
)
P1058
t
P1060 P1061
f
JOG
6.2.11 Ramp-function generator (HLG)
P1091 =...
Skip frequency 1 (entered in Hz)
Defines skip frequency 1 which avoids
effects of mechanical resonance and
suppresses frequencies within +/- P1101
(skip frequency bandwidth).
P1091 =...
Skip frequency 2
P1091 =...
Skip frequency 3
P1091 =...
Skip frequency 4
P1101 =...
Skip frequency bandwidth
(entered in Hz)
P1101
P1091
f
in
f
out
Skip frequency
bandwidth
Skip frequency
P1120 =...
Ramp-up time
(enters the accelerating time in s)
P1121 =...
Ramp-down time
(enters the deceleration time in s)
f
P1082
(f
max
)
f
1
t
P1120 P1121
P1130 =...
Rump-up initial rounding time
(entered in s)
P1131 =...
Ramp-up final rounding time
(entered in s)
P1132 =...
Rump-down initial rounding time
(entered in s)
P1133 =...
Ramp-down final rounding time
(entered in s)
P1134 =...
Rounding type
0 Continuous smoothing
1 Discontinuous smoothing
The rounding times are recommended as
abrupt responses can be avoided therefore
reducing stress and damage to the mechanical
system.
The ramp-up and ramp-down times are
extended by the component of the rounding
ramps.
P1135 =...
OFF3 ramp-down time
Defines ramp-down time from maximum frequency to standstill for OFF3 command.
10.00 s
10.00 s
5.00 Hz
5.00 Hz
2.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
0.00 Hz
10.00 s
10.00 s
5.00 s
0.00 s
0
0.00 s
0.00 s
0.00 s