Issue 04/04 6 Commissioning
MICROMASTER 420
Compact Operating Manual
19
6.2.8 Motor potentiometer (MOP)
P1031 =...
Setpoint memory of the MOP
Saves last motor potentiometer setpoint (MOP) that was active before OFF command or
power down.
0 MOP setpoint will not be stored
1 MOP setpoint will be stored (P1040 is updated)
P1032 =...
Inhibit negative MOP setpoints
0 Neg. MOP setpoint is allowed
1 Neg. MOP setpoint inhibited
P1040 =...
Setpoint of the MOP
Determines setpoint for motor potentiometer control.
MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121.
Selection
DIN
BOP
UP button
USS control word
r2032 Bit13
USS control word
r2032 Bit14
or
P0702 = 13
(DIN2)
P0703 = 14
(DIN3)
P0719 = 0, P0700 = 1, P1000 = 1
MOP up
MOP down
P0719 = 1, P0700 = 2
or
P0719 = 0, P0700 = 2, P1000 = 1
P0719 = 11
or
P0719 = 0, P0700 = 4, P1000 = 1
P0719 = 41
DOWN button
Possible parameter settings for the selection of MOP:
USS on
BOP link
USS control word
r2036 Bit13
USS control word
r2036 Bit14
or
P0719 = 0, P0700 = 5, P1000 = 1
P0719 = 51
USS on
COM link
CB control word
r2090 Bit13 r2090 Bit14
or
P0719 = 0, P0700 = 6, P1000 = 1
P0719 = 61
CB
CB control word
6.2.9 Fixed frequency (FF)
P1001 =...
Fixed frequency 1
Can be directly selected via DIN1
(P0701 = 15 16)
P1002 =...
Fixed frequency 2
Can be directly selected via DIN2
(P0702 = 15, 16)
P1003 =...
Fixed frequency 3
Can be directly selected via DIN3
(P0703 = 15, 16)
P1004 =...
Fixed frequency 4
P1005 =...
Fixed frequency 5
P1006 =...
Fixed frequency 6
P1007 =...
Fixed frequency 7
When defining the function of the digital inputs
(P0701 to P0703), three different types can be
selected for fixed frequencies:
15 = Direct selection (binary-coded)
In this particular mode, the appropriate
digital input always selects the associated
fixed frequency, e.g.:
Digital input 3 = selects fixed frequency 3.
If several inputs are simultaneously active,
then these are summed. An ON command is
additionally required.
16 = Direct selection + ON command
(binary-coded + On / Off1)
In this mode, the fixed frequencies are
selected as for 15, however these are
combined with an ON command.
17 = Binary coded selection + ON command
(BCD-coded + On/ Off1)
The BCD-coded operating mode is effective
for digital inputs 1 to 3.
P1016 =...
Fixed frequency code –
Bit 0
Defines the selection method for fixed
frequencies.
P1017 =...
Fixed frequency code –
Bit 1
P1018 =...
Fixed frequency code –
Bit 2
1 Direct selection
2 Direct selection + ON command
3 Binary coded selection + ON command
NOTE
For settings 2 and 3, all parameters P1016 to
P1019 must be set to the selected value so that
the drive inverter accepts the ON command.
0
1
5.00 Hz
5.00 Hz
10.00 Hz
15.00 Hz
20.00 Hz
25.00 Hz
30.00 Hz
0.00 Hz
1
1
1