6 Commissioning Issue 04/04
MICROMASTER 420
26 Compact Operating Manual
6.3 Series commissioning
An existing parameter set can be transferred to a MICROMASTER 420 frequency
inverter using STARTER or DriveMonitor (refer to Section 4.1 "Establishing
communications MICROMASTER 420 STARTER").
Typical applications for series commissioning include:
1. If several drives are to be commissioned that have the same configuration and
same functions. A quick / application commissioning (first commissioning) must
be carried-out for the first drive. Its parameter values are then transferred to the
other drives.
2. When replacing MICROMASTER 420 frequency inverters.
6.4 Parameter reset of factory setting
START
P0010=30
Commissioning parameter
30 Factory setting
P0970 = 1
Factory reset
0 disabled
1 Parameter reset
END
The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then
automatically exits the reset menu and sets:
P0970 = 0 : disabled
P0010 = 0 : ready
0
0

Other manuals for Siemens MICROMASTER 420