EasyManua.ls Logo

Siemens MICROMASTER 420 - Page 53

Siemens MICROMASTER 420
130 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5. SYSTEM PARAMETERS International English
MICROMASTER 420 Operating Instructions 53
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
P0003 User
Access Level
P0004 Setting
Changeable
Status
r0056 CO/BO: Status word 1 for V/f
Displays Statusword (V/f) in bit format, which can be used to diagnose inverter status.
Refer to diagram in r0052 for display layout.
Possible values:
Bit 0 Initialization control finished 0 NO
1YES
Bit 1 Motor demagnetizing finished 0 NO
1YES
Bit 2 Pulses enabled 0 NO
1YES
Bit 3 Voltage soft start select 0 NO
1YES
Bit 4 Motor excitation finished 0 NO
1YES
Bit 5 Starting boost active 0 NO
1YES
Bit 6 Acceleration boost active 0 NO
1YES
Bit 7 Frequency is negative 0 NO
1YES
Bit 8 Field weakening active 0 NO
1YES
Bit 9 Volts setpoint limited 0 NO
1YES
Bit A Slip frequency limited 0 NO
1YES
Bit b I-max controller active 0 NO
1YES
Bit C Vdc-max controller active 0 NO
1YES
Bit F Vdc-min controller active 0 NO
1YES
Note:
Refer to the bitmap diagram on page 51.
-
-
[-]
-
2
13
Europe / North AmericaP0100
Determines whether power settings (e.g. nominal rating plate power – P0307) are
expressed in kW or hp. The default settings for the nominal Motor frequency rating (P0310)
and maximum motor frequency (P1082) are also set automatically here, in addition to
reference frequency (P2000).
Possible settings:
0 = Power settings in kW; frequency default 50 Hz (Use DIP Switch 2).
1 = Power settings in hp; frequency default 60 Hz (Use DIP Switch 2)
2 = Power settings in kW; frequency default 60 Hz
Warning:
THE SETTING OF THE kW / HP DIP SWITCH UNDER THE OPERATOR PANEL WILL
OVERWRITE SETTINGS 0 OR 1 AT POWER-UP. Setting 2 will not be overwritten.
Note:
This parameter can only be changed when P0010=1 (Commissioning Mode).
0
2
[0]
-
1
1
Rated drive power [kW] or [hp]r0206
Displays the nominal motor power rating, which can be supplied by the inverter.
Note:
The display will be in kW or hp dependent on the setting of P0100
-
-
[-]
-
2
2

Table of Contents

Other manuals for Siemens MICROMASTER 420

Related product manuals