International English 5. SYSTEM PARAMETERS
60 MICROMASTER 420 Operating Instructions
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
P0003 User
Access Level
P0004 Setting
Changeable
Status
P0731 Digital output function (relay)
52.0 Inverter ready 0 Closed
1 Open
52.1 Inverter ready to run 0 Closed
1 Open
52.2 Inverter running 0 Closed
1 Open
52.3 Inverter fault active 0 Closed
1 Open
52.4 OFF2 active 0 Open
1Closed
52.5 OFF3 active 0 Open
1Closed
52.6 Switch on inhibit active 0 Closed
1 Open
52.7 Inverter warning active 0 Closed
1 Open
52.8 Deviation setpoint/actual value 0 Open
1Closed
52.9 PZD control (Process Data Control) 0 Closed
1 Open
52.A Maximum frequency reached 0 Closed
1 Open
52.b Warning: Motor overload factor 0 Open
1Closed
52.C Motor holding brake active 0 Open
1Closed
52.d Motor overload 0 Open
1Closed
52.E Motor running direction right 0 Closed
1 Open
52.F Inverter overload 0 Open
1Closed
53.0 DC brake active 0 Closed
1 Open
53.1 Inverter freq. less switch off limit (P2167 – level 3) 0 Closed
1 Open
53.2 Inverter freq. less minimum freq. 0 Closed
1 Open
53.3 Current greater or equal than limit (P2170 – level 3) 0 Closed
1 Open
53.4 Act. freq. greater comparison freq. (P2155 – level 3) 0 Closed
1 Open
53.5 Act. freq. less comparison freq. (P2155 – level 3) 0 Closed
1 Open
53.6 Act. freq. greater/equal setpoint 0 Closed
1 Open
53.7 Voltage less than threshold (P2172 – level 3) 0 Closed
1 Open
53.8 Voltage greater than threshold (P2172 – level 3) 0 Closed
1 Open
53.9 reserve 0 Closed
1 Open
53.A Controller output at lower limit (P2292) 0 Closed
1 Open
53.b Controller output at lower limit (P2291) 0 Closed
1 Open
Note
These are the most common settings. Other settings are possible in Expert mode.
0
2197.F
[52.3]-
2
7
r0752 Analog input voltage
Displays the smohthed analog input value in volts before the characteristic block
-
-
[-]
V
2
8