5. SYSTEM PARAMETERS International English
MICROMASTER 420 Operating Instructions 79
6SE6400-5AA00-0BP0
Parameter
Number
Parameter Name
Min
Max
[Default]
Units
P0003 User
Access Level
P0004 Setting
Changeable
Status
P1310 Continuous boost
Defines a level of boost to apply to both linear and quadratic V/f curves according to the
following diagram
V
V Nom
(P0304)
100%
50%
0
F Boost Min
(P1316)
F Nom
(P0310)
F Max
(P1082)
N
o
r
m
a
l
V
/
f
(
P
1
3
0
0
=
0
)
V Max
Linear V/f
V
Boost
100
V
V nom
(P0304)
50%
0
F Nom
(P0310)
F Max
(P1082)
Quadratic
V max
Normal quadratic
(P1300 = 2)
F Boost Min
(P1316, level 3)
0 V
BOOST,100
= voltage given by motor current rating (P0305)
1 * Stator Resistance (P0350)
Notes
When using Continuous Boost P1310 together with other Boost Parameters
(Acceleration Boost P1311 & Starting Boost P1312) the Boost values are combined.
However priorities are allocated to these parameters as follows :
P1310 > P1311>P1312
The achievable boost value is limited by the setting in P0640.
Increasing the Boost Levels increases the heating of the motor especially at standstill.
Σ Boosts < 300/I
mot
* R
S
0
250
[50]
%
2
13