Issue 08/03
44 Quick Start Guide MICROMASTER 440
6SE6400-5GA00-0BP0
NOTE
The 3
rd
type of parameter is a “bit” parameter. For further information on this, see the operating
instructions.
NOTE
The BOP sometimes display when changing parameter values. This means that the drive is
presently handling another higher priority task.
5.2 Factory Reset
START
P0003 = 1
User access level
1 : Access level, standard
P0010 = 30
Commissioning parameter
30 : Factory setting
P0970 = 1
Factory reset
1 : Parameter reset to the default values
P0970
The drive carries-out a parameter reset (duration, approx. 60s) and
then automatically exits the reset menu and sets
P0970 = 0 : Disabled
P0010 = 0 : Ready
NOTE
When resetting the parameters to the factory setting, the communications memory is re-initialized.
This means that communications via USS in addition to the PROFIBUS / DeviceNet / CanBus CB
board are interrupted during the reset:
The "busy" text is displayed on the BOP during the parameter reset.
After reset has been completed, communications are automatically re-established when using
STARTER, DriveMonitor or the BOP.
5.3 Commissioning an MM440
In quick commissioning you set all of the basic parameters necessary to get your motor turning. The
user must obtain all motor data information from the name plate on the motor before beginning this
process.
Here is some information about how to read the parameter data from the name plate: