4.2 Control Wiring Examples
Here are some wiring examples for your information.
On an MM440 it is important to do the commissioning in the correct order:
1. Power Cables,
2. 50/60Hz Switch
3. Control Wiring
4. Quick Commissioning
5. Other Parameters
Some example parameter settings are shown next to each picture below.
NOTE
If quick commissioning is performed after these settings shown below then the settings may be
overwritten.
Default Control Wiring
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
Default settings are shown.
No parameter changes are
needed after Quick
Commissioning
RL1
NC
RL1
NO
RL1
COM
RL2
NO
RL2
COM
RL3
NC
RL3
NO
RL3
COM
A
OUT1
+
A
OUT1
-
PTC
A
PTC
B
DIN
5
DIN
6
Iso
0V
P
+
N
-
A
OUT2
+
A
OUT2
-
10V 0V
AIN1
+
AIN1
-
DIN
1
DIN
2
Iso
24V
AIN2
+
AIN2
-
DIN
3
DIN
4
ON (UP) = 0 to 20mA
OFF = 0 to 10V
ON (UP) = 0 to 20mA
OFF = 0 to 10V
DIP SW 2
(Analog Input 2)
DIP SW 1
(Analog Input 1)
RESET
REVERSE
RUN/STOP
Analog Output
(AOUT1)
0 to 20mA
(500Ω)
? 4.7k Ω
Default control settings:
Setpoint via the AIN 1, (0-10V)
RUN command via DIN 1,
REVERSE command via DIN 2,
RESET via DIN 3,
Output frequency via AOUT 1,
Fault messages via RL1,
Warnings via RL2.