Issue 08/03
MICROMASTER 440
6SE6400-5GA00-0BP0
Quick Start Guide 39
0/4 – 20mA – Current Input
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
0-20mA
P0003=3 (Expert)
P0756[0]=2 (AIN1 – Current)
P0756[1]=2 (AIN2 – Current)
Make these additional
changes for 4-20mA
P0757[0]=4 (AIN1 min 4mA)
P0757[1]=4 (AIN2 min 4mA)
P0761[0]=4 (AIN1
Deadband)
P0761[1]=4 (AIN2
Deadband)
NOTE:
Index [0] is AIN1, Index [1] is
AIN2, so if you are only
using 1 Analog Input then
you only need to change
those indices.
ON (UP) = 0 to 20mA
OFF = 0 to 10V
ON (UP) = 0 to 20mA
OFF = 0 to 10V
DIP SW 2
(Analog Input 2)
DIP SW 1
(Analog Input 1)
0 – 20mA or
4 – 20mA
RL1
NC
RL1
NO
RL1
COM
RL2
NO
RL2
COM
RL3
NC
RL3
NO
RL3
COM
A
OUT1
+
A
OUT1
-
PTC
A
PTC
B
DIN
5
DIN
6
Iso
0V
P
+
N
-
A
OUT2
+
A
OUT2
-
10V 0V
AIN1
+
AIN1
-
DIN
1
DIN
2
Iso
24V
AIN2
+
AIN2
-
DIN
3
DIN
4
0 – 20mA or
4 – 20mA
0 to 10V (Voltage Input)
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
These are the default
settings as shown. No
parameter changes are
necessary other than quick
commissioning.
RL1
NC
RL1
NO
RL1
COM
RL2
NO
RL2
COM
RL3
NC
RL3
NO
RL3
COM
A
OUT1
+
A
OUT1
-
PTC
A
PTC
B
DIN
5
DIN
6
Iso
0V
P
+
N
-
A
OUT2
+
A
OUT2
-
10V 0V
AIN1
+
AIN1
-
DIN
1
DIN
2
Iso
24V
AIN2
+
AIN2
-
DIN
3
DIN
4
ON (UP) = 0 to 20mA
OFF = 0 to 10V
ON (UP) = 0 to 20mA
OFF = 10V
DIP SW 2
(Analog Input 2)
DIP SW 1
(Analog Input 1)
≥ 4.7k Ω
≥ 4.7k Ω