Issue 08/03
40 Quick Start Guide MICROMASTER 440
6SE6400-5GA00-0BP0
2-Wire Control
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
These are the default settings
as shown. No parameter
changes are necessary other
than quick commissioning.
RL1
NC
RL1
NO
RL1
COM
RL2
NO
RL2
COM
RL3
NC
RL3
NO
RL3
COM
A
OUT1
+
A
OUT1
-
PTC
A
PTC
B
DIN
5
DIN
6
Iso
0V
P
+
N
-
A
OUT2
+
A
OUT2
-
10V 0V
AIN1
+
AIN1
-
DIN
1
DIN
2
Iso
24V
AIN2
+
AIN2
-
DIN
3
DIN
4
RUN/STOP
Switch
When switch is closed,
drive will RUN, it will
STOP when switch is
opened
ON (UP) = 0 to 20mA
OFF = 0 to 10V
ON (UP) = 0 to 20mA
OFF = 0 to 10V
DIP SW 2
(Analog Input 2)
DIP SW 1
(Analog Input 1)
3-Wire Control (Using BICO for Latching)
Parameter Settings:
Make these changes
AFTER quick
commissioning: see
section 5.5 on page 42
P0003=3 (Expert)
P0700[0]=2
P0701[0]=99 (BICO)
P0702[0]=99 (BICO)
P0840[0]=2841 (output of RS
Flip Flop 1)
P0844[0]=722.1
P2800=1 (Enable FFBs)
P2801[9]=1 (Enable NOT1)
P2801[14]=1 (Enable RS
FF1)
P2828=722.1 (Invert DIN2)
P2840[0]=722.0 (Set)
P2840[1]=2829.0 (Reset)
NOTE:
This method works by
creating a latch from a flip
flop. It is set from DIN1 and
reset from DIN2
RL1
NC
RL1
NO
RL1
COM
RL2
NO
RL2
COM
RL3
NC
RL3
NO
RL3
COM
A
OUT1
+
A
OUT1
-
PTC
A
PTC
B
DIN
5
DIN
6
Iso
0V
P
+
N
-
A
OUT2
+
A
OUT2
-
10V 0V
AIN1
+
AIN1
-
DIN
1
DIN
2
Iso
24V
AIN2
+
AIN2
-
DIN
3
DIN
4
STOP
START
START
Normally Open Push Button
(Momentary Action)
STOP
Normally Closed Push Button
(Momentary Action)
Wiring when BICO
performs the
“latching” process
www . ElectricalPartManuals . com