5.5 Level 3 Quick Commissioning
Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to
the parameter list on the supplied CD for additional setting possibilities.
Correct Motor information is very important – please refer to section 5.4 for detailed information. For
multi-motor (parallel motors) please see the operating instructions for further details.
Parameters with “[0]” after the number are referring to index 0 of that parameter. For example, if you
read P0300[0]=1 it means that you should set P0300 index 0 to a 1.
You can enter your own settings in the user settings column for quick reference
Parameter
Number
Parameter Description Suggested
Setting
User
Setting
P0003 Set User Access Level *
1 Standard
2 Extended
3 Expert
3
P0010
Start Quick Commissioning *
0 Ready
1 Quick commissioning
30 Factory setting (refer to section 5.2)
NOTE
P0010 must be set to 1 in order to parameterize the
motor data.
1
P0100
Check/Set Frequency Setting (50/60Hz)
0 USE DIP2(2) Switch - 50Hz, kW (typically
European IEC Motors)
1 USE DIP2(2) Switch - 60 Hz, HP (typically North
American NEMA frame motors)
2 60 Hz, kW (Typically found in Asian market)
IMPORTANT
NOTE:
For P0100 = 0 or 1, the setting of switch DIP2(2) (under
I/O board) determines the value of P0100 (refer to the
parameter list):
OFF = kW, 50 Hz
ON = HP, 60 Hz
If P0100 does not correctly reflect your motor data
(50/60Hz) at this point, please power down your
MICROMASTER and change the DIP2(2) switch
according to section 3 before continuing.
Failure to follow this procedure will result in
complete loss of your motor parameters at the next
power cycle.
According
to motor
usually a
“1” should
be set
using the
DIP2(2)
switch in
the USA