5.8 Setting up Inputs and Outputs,
5.8.1 Digital inputs (DIN)
Parameter range
r0701 – P0725
Features:
Quantity 6
Cycle time 2 ms
Switch-on threshold 13.6 V
Switch-off threshold 10.6 V
Electrical features electrically isolated, short-circuit proof
Function chart number FP2000, FP2200 (in parameter list)
Table 5-4 Digital Input Specification
External control signals are required for a drive to be able to operate. These signals can be entered
through the serial interface as well as using digital inputs.
MICROMASTER 440 has 6 digital inputs which can be expanded to a total of 8 by using the 2 analog
inputs. The digital inputs can be freely programmed to create a function. It is possible to directly assign
a pre-designed function using parameters P0701 - P0708 or to build your own function using BICO
technology.
This document will only cover the use of the pre-designed functionality.
or
24 V
T0
&
0
1
PNP/NPN DIN
0... 1
P0725 (1)
0 V
24V
Debounce time: DIN
0... 3
P0724 (3)
CO/BO: Bin.inp.val
r0722
r0722
.x
Function
T9 P24 (PNP)
T28 0 V (NPN)
Pxxxx BI: ...
P070x
Figure 5-5 Digital Inputs Function Diagram
The diagram above illustrates that you have external switches. You choose whether the signals are
active high or active low (P0725). You choose the de-bounce time to filter out noisy switches (P0724),
you then assign a function to that input according to the table 5.8 below (P0701-P0708);
NOTE
r0722 is a digital representation of the status of the 6 (+2) digital inputs – this parameter should be
used to check that your signals are coming through to the drive.