54 Quick Start Guide MICROMASTER 440
6SE6400-5GA00-0BP0
Please refer to the troubleshooting section for information on how to use r0722.
Parameters P0701 – P0706 (P0707 – P0708)
Parameter
value
Function
0 Digital input disabled
1 ON / OFF1
2 ON+reverse / OFF1
3 OFF2 – coast to standstill
4 OFF3 – quick ramp-down
9 Fault acknowledge
10 JOG right
11 JOG left
12 Reverse
13 MOP up (increase frequency)
14 MOP down (decrease frequency)
15 Fixed setpoint (direct selection)
16 Fixed setpoint (direct selection + ON)
17 Fixed setpoint (binary-coded selection + ON)
25 Enable DC braking
29 External trip
33 Disable additional frequency setpoint
99 Enable BICO parameterization
Table 5-6 Standard Selectable Functions for Digital Inputs
NOTE
If an analog input has been configured as digital input, then the following limit values apply:
< 1.7 V DC = "0", > 3.9 V DC = "1"
BICO parameterization
If the available settings above are not sufficient for your application, then refer to the operating
instructions and parameter lists for comprehensive information about BICO parameterization.
NOTE
Only experienced users should use the BICO parameterization and for applications where the
possibilities provided by P0701 – P0708 are no longer adequate.