Issue 08/03 
 
54  Quick Start Guide  MICROMASTER 440 
6SE6400-5GA00-0BP0
 
Please refer to the troubleshooting section for information on how to use r0722. 
 
Parameters P0701 – P0706 (P0707 – P0708) 
 
Parameter 
value 
Function 
0 Digital input disabled 
1  ON / OFF1 
2  ON+reverse / OFF1 
3  OFF2 – coast to standstill 
4  OFF3 – quick ramp-down 
9 Fault acknowledge 
10 JOG right 
11 JOG left 
12 Reverse  
13  MOP up (increase frequency) 
14  MOP down (decrease frequency) 
15  Fixed setpoint (direct selection) 
16  Fixed setpoint (direct selection + ON) 
17  Fixed setpoint (binary-coded selection + ON) 
25  Enable DC braking 
29 External trip 
33  Disable additional frequency setpoint 
99  Enable BICO parameterization 
Table 5-6 Standard Selectable Functions for Digital Inputs 
NOTE 
If an analog input has been configured as digital input, then the following limit values apply:   
< 1.7 V DC = "0", > 3.9 V DC = "1"
 
 
BICO parameterization 
 
If the available settings above are not sufficient for your application, then refer to the operating 
instructions and parameter lists for comprehensive information about BICO parameterization. 
 
NOTE
 
Only experienced users should use the BICO parameterization and for applications where the 
possibilities provided by P0701 – P0708 are no longer adequate.   
 