EasyManua.ls Logo

Siemens MICROMASTER 440 - Page 55

Siemens MICROMASTER 440
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Issue 08/03
MICROMASTER 440
6SE6400-5GA00-0BP0
Quick Start Guide 55
5.8.2 Analog inputs (ADC)
Parameter range
P0750 – P0762
Features:
Quantity 2
Cycle time 4 ms
Resolution 10 bits
Accuracy 1% of full scale (10V or 20mA)
Electrical features Polarity protection, short-circuit proof
Function chart number FP2200 (in parameter list)
Table 5-7 Analog Input Specifications
Analog signals are converted to digital signals inside the drive using Analog to Digital Converters.
The user must select either Voltage (default) or Current using the 2 switches on the I/O board
DIP1(1,2). Additionally, P0756 must also be set accordingly.
Example using voltage input
RL1
NC
RL1
NO
RL1
COM
RL2
NO
RL2
COM
RL3
NC
RL3
NO
RL3
COM
A
OUT1
+
A
OUT1
-
PTC
A
PTC
B
DIN
5
DIN
6
Iso
0V
P
+
N
-
A
OUT2
+
A
OUT2
-
10V 0V
AIN1
+
AIN1
-
DIN
1
DIN
2
Iso
24V
AIN2
+
AIN2
-
DIN
3
DIN
4
ON (UP) = 0 to 20mA
OFF = 0 to 10V
ON (UP) = 0 to 20mA
OFF = 0 to 10V
DIP SW 2
(Analog Input 2)
DIP SW 1
(Analog Input 1)
≥ 4.7k Ω
≥ 4.7k Ω
Possible settings of P0756:
0 Unipolar voltage input ( 0 to 10 V )
1 Unipolar voltage input with monitoring (0 to 10 V )
2 Unipolar current input (0 to 20 mA)
3 Unipolar current input with monitoring (0 to 20 mA)
4 Bipolar voltage input (-10 V to +10 V) (only AIN1)
Figure 5-8 DIP Switch And P0756 for Analog Voltage Input
www . ElectricalPartManuals . com

Other manuals for Siemens MICROMASTER 440