50 Quick Start Guide MICROMASTER 440
6SE6400-5GA00-0BP0
Parameter
Number
Parameter Description Suggested
Setting
User
Setting
P1121[0]
Set Ramp-Down Time
Enters the time with which, for example, the motor should
brake from the maximum frequency P1082 down to
standstill. If the ramp-down time is set too low, then this
may result in alarms A0501 (current limit active), A0502
(overvoltage limit active) or the drive tripping with fault
F0001 (overcurrent) or F0002 (overvoltage).
10
P1135[0]
Set OFF 3 Ramp-Down Time
Enters the time with which, for example, the motor should
brake from the maximum frequency P1082 down to
standstill with an OFF3 Command (Fast Stop). If the ramp-
down time is set too low, then this may result in alarms
A0501 (current limit active), A0502 (overvoltage limit active)
or the drive tripping with fault F0001 (overcurrent) or F0002
(overvoltage).
5
P1300[0]
Select Control Mode
0 V/f with linear characteristic
1 V/f with FCC
2 V/f with parabolic characteristic
5 V/f for textile applications
6 V/f with FCC for textile applications
19 V/f control with independent voltage setpoint
20 Sensorless Vector control **
21 Vector control with sensor **
22 Sensorless Vector torque-control **
23 Vector torque-control with sensor **
NOTE
** See Parameter List document for further information
on any non-V/f control mode.
0
P1500[0]
Select Torque Setpoint *
0 No main setpoint
2 Analog setpoint
4 USS on BOP link
5 USS on COM link (control terminals 29 and 30)
6 CB on COM link (CB = communications module)
7 Analog setpoint 2
0
WARNING
The motor data identification routine must not be used for loads which are
potentially hazardous (e.g. suspended loads for crane applications). Before
the motor data identification run is started, the potentially hazardous load must
be carefully secured (e.g. by lowering the load to the floor or by clamping the
load using a motor holding brake).