Issue 08/03
58 Quick Start Guide MICROMASTER 440
6SE6400-5GA00-0BP0
5.8.4 Commonly Used Relay Functions
Use the settings below in P0731 – P0733 to get the described functionality
Parameter value Function
52.0 Drive ready
52.1 Drive ready to run
52.2 Drive running
52.3 Drive fault active
52.4 OFF2 active
52.5 OFF3 active
52.6 Switch-on inhibit active
52.7 Drive warning active
52.8 Deviation, setpoint / actual value
52.9 PZD control (Process Data Control)
52.A Maximum frequency reached
52.B Warning: Motor current limit
52.C Motor holding brake (MHB) active
52.D Motor overload
52.E Motor running direction right
52.F Drive overload
53.0 DC brake active
53.1 Act. frequency f_act >= P2167 (f_off)
53.2 Act. frequency f_act > P1080 (f_min)
53.3 Act. current r0027 >= P2170
53.6 Act. frequency f_act >= setpoint
Table 5-12 Common Relay Functions
NOTE
Parameter Values above refer to r0052 and r0053 values.
A complete list of all of the connectable parameters may be taken from the parameter list (on the CD
that was supplied with the MM440 drive).