Structure & function
20
Building Technologies 007798_g_en NK8000 ICC.doc
Fire Safety & Security Products 06.2006
4.1.2 Guide to front panel
The front panel of the NK822x houses 9 LED's.
The five LED's on the left side are, from top to bottom:
Front panel LED Functions
Power (LED green) Power (hardware controlled)
Vital functions (LED green) Software vitality (blinking)
Tamper (LED bicolour) Unit tamper:
Red means tamper alarm (hardware controlled)
Green means tamper disabled (from management station)
Download (LED red) NK822x network diagnostics:
Off = Status OK
Blinking (1 flash) = Missing identification from NS8210
Blinking (2 flashes) = Download in progress from NS8210
Blinking (3 flashes) = Default mode ( switch settings in
section 4.1.3): FTP channel open
On = Critical/hardware fault
Diagnostic (LED yellow) NK822x internal interface diagnostics:
Off = Status OK
Blinking (1 flash) = Missing or insufficient license
Blinking (2 flashes) = Trouble with the I
2
C bus to I/O modules
Blinking (3 flashes) = Trouble with the LON interface
Blinking (4 flashes) = Trouble with the serial/network interface
Blinking (5 flashes) = Trouble with DLL or RCLOCK file(s)
On = Critical/hardware fault
LED functions on the front panel, left side
The four LED's on the right side are, from top to bottom:
Front panel LED (right Functions
Com1 Status Com1
Com2 Status Com2
Com3 Status Com3
Com4 Status Com4
Red: RX
Green: TX
LED functions on the front panel, right side