11 Technical data
11.1 NK8223 / NK8222 Ethernet Ports
Lines to local host
1 RS232 line
– Transport protocol: CMSDL
– Host (single host only):
– MM8000 or MK8000 equipped with NS8012
CDI-Net Driver
– MT8001
Up to 9600 baud
Lines to remote host(s)
1 Ethernet IEEE 802.3, 10Base-T
– Transport protocol: CEI 79-5B
– Host (single host only):
– MM8000 or MK8000, equipped with NS8210
Network Driver (supporting up to 100
NK822x)
– FEAL 64-bit encryption
or
– Transport protocol: CMSDL/IP
– Hosts (up to four):
– MM8000 and/or MK8000, equipped with
NS8210 Network Driver (supporting up to
100 NK822x)
10Mbit/sec
Switched lines to remote host
(as backup line)
Not yet available
Lines to subsystems
LON line and 2/4 RS232 lines, protocol and baud rate
options configured by NK8000- configuration tool
(Composer):
– CNAP protocol (CS6 MP3)
– Cerban protocol (CS114x EP5 and EP7F, CZ10,
CZ12, CS4, CS440, CC60)
– Sintony serial link protocol (SI410)
– ISO1745 protocol (Connection to Cerloop via
MK7022: CS114x EP5 and EP7F, CZ10, CZ12,
CS4, CS440, CC60, STT2410, STT11, STT20,
DMS7000 units)
– ISO1745 direct protocol (CS114x, FC700A)
– CMXDL protocol (CF9003)
– Burle protocol (Philips-Burle)
– CDDL/CDSF (Siemens Simatrix)
– CDDL/CDSF (other control units)
– SDN-T/VBF (D100, SIGMASYS)
LON: 78Kbit/sec
RS232: 300 or 600 baud
RS232: 9600 baud
RS232: 1200 or 2400 baud
RS232: 1200 or 2400 baud
RS485: 9600 baud
RS232: up to 9600 baud
RS232: 2400 baud
RS232: up to 9600 baud
RS232 4800, 9600 baud
Interactions
Programmable interaction programs including single
or multiple triggers (incoming events) and single or
multiple effects (outgoing control actions). Interactions
are possible between locally connected subsystems.
– Subsystems supported: CS11 AlgoRex, CS6 MP3,
SI410 Sintony, CF9000, Philips-Burle, SIGMASYS,
D100
– Logical combinations: AND, OR, XOR, NOT
– Delay of effects (wait): configurable 0…6500 sec.
– Max. # of interactions: 1000
– Total # of field points used in triggers/effects: 5000
– Max. # of field points/interactions that can be com-
bined in a trigger expression: 255
Ethernet data traffic
Very low network load:
– Keep-alive message: 1 empty TCP/IP packet
– Periodic authentication: exchange of three CEI
packets with max. 30 bytes
– Single alarm event: from 20 to 60 bytes
Configurable, default every 30 s
Configurable, default 10 min.
Connectors
– D-Sub 9 pin, female type (for serial and modem
lines)
– RJ-45 connector for Ethernet
– Wieland 5-pin connector for power supply and LON
Cables
– RS232 lines: two unshielded twisted pairs
– LON line: one unshielded twisted pair
Cat.3 UTP, max. 15 m
Cat.4 UTP, 22AWG
Max 500 m (free topology)
Max 1400 m (doubly terminated bus topology)