7.2 Configuring NK822x IP – via NW8202
This configuration must be performed before the NK822x(s) can be configured at
the client’s site. This procedure details how to send the IP configuration informa-
tion; that is, the IP address, Subnet mask, and Default address to the NK822x via
the NW8202 Tool.
Note: This configuration procedure can be performed prior to shipping the NK822x
to the client, or at a later time at the client’s site.
1. Set the Service PC IP address to 192.168.9.1 and the subnet mask to
255.255.255.0.
a. Select Start Settings Network and Dial Up Connections.
b. Double-click Local Area Connection.
c. Click the Properties button.
d. Select Internet Protocol (TCP/IP).
e. Click the Properties button.
f. Make note of the current IP address before replacing it with the new one.
2. Click OK to restart PC when prompted.
3. Remove the cover of the NK822x to be configured (press the 4 white tabs to the
rear of the left and right sides of the unit and lift gently).
4. Open the NW8202 application by selecting NW8202.exe located in the C: \
MM8000 or MK8000 <InstallDir>\Utilities\NW8202 folder.
5. Select the Firmware Version.
6. Enter the new IP address, Subnet mask, and Default gateway in the appropriate
fields (see Fig. 28).
Fig. 28 NW8202 IP configuration download tool
7. Click Download.
The Download Procedure window is displayed. (See Fig. 29.)
8. Follow the instructions displayed.