Building Technologies Division User Manual RWF55... CC1U7867en
Infrastructure & Cities Sector 3 Installation 05.11.2013
3.3 Side-by-side mounting
If several controllers are mounted side-by-side or above one another in a control panel,
the horizontal distance between panel cutouts must be a minimum of 11 mm and the
vertical distance a minimum of 50 mm.
3.4 Mounting the controller in a panel cutout
*
Remove the mounting clips
*
Fit the seal supplied with the controller
Attention!
The controller must be installed with the seal, preventing water or dirt from
entering the housing!
(2)
(3)
(1)
(3)
(2)
7867z02/0612
Figure 3: Mounting in a panel cutout
*
Insert the controller from the front into the panel cutout (1) and make certain the seal
is correctly fitted
*
Working from the rear side of the panel, push the mounting clips into the guide slots
on the side of the controller (2) and tighten them evenly using a screwdriver (3) until
the controller housing is seated firmly in the panel cutout.