5.2.3  2-stage burner, 3-position output  
 
In area (1), the thermostat function is active. In area (2), the RWF55 as a 2-position 
controller acts on the second stage via relay K2 (OPEN) and relay K3 (CLOSE) by 
switching on at switch-on threshold HYS1 and switching off at switch-off threshold HYS2. 
 
7866d07/0911
 
Figure 10: Control sequence of 2-stage burner, 3-position output 
 
In area (3), the actual value exceeds the upper switch-off threshold HYS3 and the 
controller shuts down the burner (B). The controller only starts low-fire operation when 
the actual value falls again below switch-on threshold HYS1. If the response threshold 
(q) is exceeded, the controller switches to high-fire operation (A). 
 
 
Reference! 
See chapter 5.6 Response threshold (q).