Building Technologies Division User Manual RWF55... CC1U7867en
Infrastructure & Cities Sector 5 Operating modes 05.11.2013
5.4.1 Setpoint changeover SP1 / SP2 or setpoint shift analog via
InP2
InP3
(outside temperature)
FnC3
= 0 no function
binI
= 2
binI
= 1
binI
= 0 / 3
Function = 2
InP2 FnC2
:
SPL oLLo
/
A
ctive setpoint
SPH oLHi
/
Heating curve
Factory setting: = -10,
= 60, = 20, = 50
At1
Ht1 At2 Ht2
Function :
InP3
InP3
See chapter 8.3 Analog input
Function of binary input D1:
Setpoint changeover:
0 1
2 0
1
Binary input circuit D1:
See chapter 4.3 Assignment of terminals
See chapter 7 Parameterization
PArA
See chapter 5.5 Weather compensated
setpoint shifting
See chapter 8.3 Analog input
InP3
Figure 12: Setpoint changeover or setpoint shift