6.5 Manual control, 2-stage burner
Note!
Manual control can only be activated if the thermostat function active relay K1. If the
thermostat function inactive relay K1 during manual control, manual control is ended.
*
Press for 5 seconds
*
Press briefly
Relay K2 / K3 Analog output A- / A+
Relay K2 is active
Relay K3 is inactive
The analog output delivers the highest value
(depending on setting DC 10 V or 20 mA)
Controlling element opens
*
Or press briefly
Relay K2 / K3 Analog output A- / A+
Relay K2 is inactive
Relay K3 is active
The analog output delivers the lowest value
(depending on setting DC 0 V, 4 mA, or
0 mA)
Controlling element closes
*
Return to automatic operation by pressing for 5 seconds