52/93 
Building Technologies Division  User Manual RWF55...  CC1U7867en 
Infrastructure & Cities Sector  8 Configuration ConF  05.11.2013 
8.2 Analog input InP2  
 
This input can be used to specify an external setpoint or carry out setpoint shifting. 
 
ConF  InP  InP2  
 
Parameter Value/ 
selection 
Description 
Function 
FnC2 
0 No function 
1 External setpoint (display SPE) 
2 Setpoint shifting (display dSP) 
3 Angular positioning feedback 
Sensor type 
SEn2 
Sensor type 
1 0...20 mA 
2 4...20 mA 
3 0...10 V 
4 0...5 V 
5 1...5 V 
6 Resistance teletransmitter 
Correction of 
measured value 
OFF2 
Offset 
-1999... 
0... 
+9999 
Using the measured value correction function (offset), a measured value can 
be corrected by a certain amount, either up or down. 
 
Example: 
 
Measurement value  Offset  Display value 
294.7   +0.3  295.0 
295.3   -0.3  295.0 
 
Caution! 
Measured value correction:  
To make the calculation, the controller uses the corrected value (displayed value). This value does not 
represent the value acquired at the point of measurement.  
If the measured value correction function is used incorrectly (e.g., overcompensation of measured values 
 measurement error only present temporarily), this may lead to undesirable plant states. 
Start of display 
SCL2 
Scale low level 
 
 
-1999... 
0... 
+9999 
In the case of a measuring transducer with standard signal, the physical 
signal is assigned a display value here. 
 
Example: 0…20 mA = 0…1500 °C 
 
The physical signal range can be undershot/exceeded by 20% without a 
measuring range overshoot/undershoot signal being issued. 
End of display 
SCH2 
Scale high level 
-1999... 
100... 
+9999 
Filter time constant 
dF2 
Digital filter 
0.0... 
2... 
100.0... 
Is used to adapt the digital 2nd order input filter (time in s; 0 s = filter off). 
 
If the input signal changes abruptly, about 26% of the change is captured 
after a time corresponding to the filter time constant dF (2 x dF: approx. 59%; 
5 x dF: approx. 96%). 
 
If the filter time constant is large: 
- High attenuation of interference signals 
- Slow response of actual value display to changes in the actual value 
- Low limit frequency (low-pass filter)