68/93 
Building Technologies Division  User Manual RWF55...  CC1U7867en 
Infrastructure & Cities Sector  11 Modbus interface  05.11.2013 
11 Modbus interface 
 
The tables that follow in this chapter specify the addresses of the readable and writable 
words that the customer is able to access. The customer may read and/or write the 
values using SCADA programs, PLCs, or similar. 
 
The entries under Access have the following meanings: 
 
R/O Read Only, value can only be read 
R/W Read/Write, value can be read and written 
 
The number of characters specified under Data type in the case of character strings 
includes the final \0. 
 
Char10 means that the text is up to 9 characters long. The final \0 character is then 
added to this. 
 
11.1 User level  
 
Address  Access  Data type  Signal reference  Parameter 
0x0000 R/O  Float  X1  Analog input InP1 
0x0002 R/O  Float  X2  Analog input InP2 
0x0004 R/O  Float  X3  Analog input InP3 
0x0006 R/O  Float  WR  Actual setpoint 
         
0x0008 R/W  Float 
SP1 
Setpoint 1 
0x000A R/W  Float  SP2 (= dSP) Setpoint 2 
         
0x1035 R/O  Float  ---  Analog input InP3 
(unfiltered) 
0x1043 R/O  Float  ---  Actual angular 
positioning 
0x1058 R/O  Word  B1  Burner alarm 
 
Example: