5.2.2  Modulating burner, analog output 
 
 
 
Thermostat function active. 
 
The RWF55 as a modulating controller provides control to the adjusted setpoint. 
Angular positioning is ensured via the analog output in the form of a standard signal. 
 
A
7866d06/0911
 
Figure 9: Control sequence of modulating burner, analog output 
 
The controller behaves as described in chapter 5.2.1 Modulating burner, 3-position 
output.
 
 
If the controller is set to cooling mode, the respective values HYS4 and HYS6 apply. 
 
Starting from a high actual value, the controller now controls the connected cooling 
equipment in low-fire operation. In high-fire operation, the cooling output is controlled 
via relays K2 and K3 or the analog output. The response threshold (q) calculates 
automatically (now in the reverse sense) the point from which the cooling output is to 
be increased. 
 
Angular positioning is ensured via the analog output in the form of a standard signal. 
 
 
Note! 
The modulating controller must be configured. 
 
 
Reference! 
See chapter 8.4 Controller 
Cntr
 
 
rea (1)  
rea (2)  
rea (3)  
Cooling controller 
Output