61/93 
Building Technologies Division  User Manual RWF55...  CC1U7867en 
Infrastructure & Cities Sector  8 Configuration ConF  05.11.2013 
8.10 Interface IntF 
 
The controller can be integrated into a data network using an optional RS-485 interface 
or an optional Profibus DP interface. 
 
ConF  IntF  
 
Parameter Value/ 
selection 
Description 
Baud rate 
bdrt 
Baud rate 
0 4800 Baud 
1 9600 Baud 
2 19200 Baud 
3 38400 Baud 
Device address 
Modbus 
Adr 
Device address 
0... 
1... 
254 
Address in the data network 
Device address 
Profibus 
dP 
Device address 
0...125 
Only RWF55.6 
Remote Detection 
Timer 
dtt 
Remote detection timer 
0...  0 = Switched-off 
30... 
7200 s 
 
 
Note! 
If communication is taking place via the setup interface, the other interfaces are 
inactive.