69/93
Building Technologies Division User Manual RWF55... CC1U7867en
Infrastructure & Cities Sector 11 Modbus interface 05.11.2013
11.2 Parameter level
Address Access Data type Signal reference Parameter
0x3000 R/W Float
Pb1
Proportional range 1
0x3004 R/W Float
dt
Derivative action time
0x3006 R/W Float
rt
Integral action time
0x300C R/W Float
db
Dead band
0x3012 R/W Word
tt
Controlling element
running time
0x3016 R/W Float
HYS1
Switch-on threshold
0x3018 R/W Float
HYS2
Switch-off threshold
down
0x301A R/W Float
HYS3
Switch-off threshold up
0x301C R/W Float
HYS4
Switch-on threshold
(cooling)
0x301E R/W Float
HYS5
Switch-off threshold
down (cooling)
0x3020 R/W Float
HYS6
Switch-off threshold up
(cooling)
0x3022 R/W Float
q
Reaction threshold
0x3080 R/W Float
At1
Outside temperature 1
0x3082 R/W Float
Ht1
Boiler temperature 1
0x3084 R/W Float
At2
Outside temperature 2
0x3086 R/W Float
Ht2
Boiler temperature 2