14 Technical data 
 
 
14.1 Inputs 
14.1.1 Analog input InP1 (actual value)  
 
For resistance thermometers, thermal elements or standard signals with 2nd order 
digital filters (configurable). 
 
Sampling time  250 ms 
 
Type Measuring  
range 
Measuring 
accuracy 
a
 
Impact of 
ambient  
temperature 
Pt100; DIN EN 60751  -200...850 °C 
(-328...1562 °F) 
0,05% 
50 ppm/K 
Pt1000; DIN EN 60751  -200...850 °C 
(-328...1562 °F) 
0,05% 
50 ppm/K 
LG-Ni1000   -50...+160 °C 
(-58...320 °F) 
0,05% 
50 ppm/K 
0...135  
0,05% 
50 ppm/K 
a
 Accuracies relate to the maximum measuring range.  
 
Line resistance  Max. 30  per line with 3-wire circuit 
Line balancing  Not required with 3-wire circuits. 
With 2-wire circuits, line balancing can be 
performed by making an actual value 
correction 
 
Type 
Measuring  
range
 
Measuring 
accuracy 
a 
Impact of ambient  
temperature 
Fe-CuNi J  
DIN EN 60584 
-200...+1200 °C  
(-328...+2192 °F) 
0.25%  100 ppm/K 
NiCr-Ni K 
DIN EN 60584 
-200...+1372 °C  
(-328...+2502 °F) 
0.25%  100 ppm/K 
Cu-CuNi T 
DIN EN 60584 
-200...+400 °C  
(-328...+752 °F)  
0.25%  100 ppm/K 
NiCrSi-NiSi N 
DIN EN 60584 
-100...+1300 °C  
(-148...+2372 °F) 
0.25%  100 ppm/K 
Pt-RhPt S 
DIN EN 60584 
-50...+1768 °C  
(-58...+3214 °F)  
0.25%  100 ppm/K 
Pt-RhPt R 
DIN EN 60584 
-50...+1768 °C  
(-58...+3214 °F)  
0.25%  100 ppm/K 
Pt-RhPt B 
DIN EN 60584 
0...1820 °C  
(32...3308 °F)  
0.25%  100 ppm/K 
a
 Accuracies relate to the maximum measuring range.  
 
Cold-function temperature  Internal 
 
Resistance 
thermometers 
Thermal elements