File management and file access with FTP/FTPS
9.3 Advanced CP as FTP server for the S7 CPU data
Configuring and commissioning S7 CPs for Industrial Ethernet
154 Configuration Manual, 09/2013, C79000-G8976-C182-13
Notes on the syntax
Relevant rows can be recognized by the "cpux" string (where x = characters "14"); this
applies to both areas.
Note
Notation
Note the use of lower-case letters. Otherwise the files will not be recognized.
Use a text editor that does not create invisible control characters or save the data in
the TXT mode so that no invisible control characters are stored.
Valid delimiters for the entries are "blanks".
All other characters are interpreted as comment characters.
The following applies to the file name of a file DB:
Length: maximum 64 characters;
Permitted characters: letters "A−Z,a−z"; digits "0−9", "_", "."
Row length: maximum 256 characters
Example
In the example shown here, the FTP command C:> PUT s7daten.txt cpu1db35 is used to
transfer the s7daten.txt file to DB35 (file DB) that must be located on CPU1.