Configuring the Ethernet CP with STEP 7
3.3 Setting further CP properties
Configuring and commissioning S7 CPs for Industrial Ethernet
60 Configuration Manual, 09/2013, C79000-G8976-C182-13
●
– The following applies to both areas:
Relevant rows can be recognized by the "cpux" string (where x = characters "1-4").
This applies to both areas.
Valid delimiters for the entries are "blanks".
All other characters are interpreted as comment characters and start a comment up to
the end of the row
Row length: maximum 256 characters
– The following applies to the file name of a file DB:
The file name begins with "cpuX" (where X=1, 2, 3, or 4);
"cpuX" must first be defined in the rack/slot assignment of the CPU;
Length: maximum 64 characters (including "cpuX");
Maximum of 100 entries;
Permitted characters: letters "A-Z,a-z"; digits "0-9", "_", "."
● Mixing entries
You can also mix the entries for rack/slot assignment of the CPU and DB assignment.
The DB assignment must, however, always come
the rack/slot assignment of the
relevant CPU.
You could therefore enter the example as follows:
The following entry is, however, not permitted and would be rejected with an error message:
Note
Remember the notation:
•
Please note the capitalization (lower case for "cpu" and no leading blanks at the
beginning of the row). Otherwise the files will not be recognized.
The tabulator is
permitted as separator.