Product Characteristics
4.2 SCALANCE X101-1
4.2.4 SCALANCE X101-1 TP Port
Connector Pinout
RJ-45 jack
Figure 4-2 RJ-45 connector pinout
Pin number Pinout
Pin 8 NC
Pin 7 NC
Pin 6 TD-
Pin 5 NC
Pin 4 NC
Pin 3 TD+
Pin 2 RD-
Pin 1 RD+
On SCALANCE X101-1, the twisted pair port is implemented as RJ-45 jack with MDI-X
assignment (Medium Dependent Interface–Autocrossover) of a network component.
Notice
TP cords or TP-XP cords with a maximum length of 10 m can be connected to the RJ-45 TP
port.
Depending on the cable type, a total cable length of up to 100 m is permitted between two
devices with the IE FC cables and IE FC RJ-45 plug 180.
Autonegotiation
Autonegotiation means the automatic detection of the functionality of the port at the opposite
end. Using autonegotiation, repeaters or DTEs can detect the functionality available at the
port of a partner device allowing automatic configuration of different types of device. With
autonegotiation, two components connected to a link segment can exchange parameters
and set themselves to match the supported communication functionality.
Industrial Ethernet Media Converters SCALANCE X-100 Series
4-4 Commissioning Manual, 07/2008, A2B00051521A

Table of Contents

Other manuals for Siemens SCALANCE X101-1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SCALANCE X101-1 and is the answer not in the manual?

Siemens SCALANCE X101-1 Specifications

General IconGeneral
BrandSiemens
ModelSCALANCE X101-1
CategoryMedia Converter
LanguageEnglish

Related product manuals