Service and maintenance
11.1 Preventive measures
3VL molded-case circuit breakers
142 System Manual, 03/2009, 110 0110 - 02 DS 01
Check connections are tight
Check the terminal screws for proper torque values
Spot checking of input and output cables
Spot checking of terminal accessories
Replace damaged terminal accessories after cleaning the terminal area
Check, and, if necessary, correct, the settings of the electronic overcurrent trip unit in
accordance with the system conditions
Electronic circuit breaker releases must only be tested with a device especially
supplied for this purpose.
The operator (customer) must arrange for the disposal of the molded-case circuit breaker or
the replaced parts at the end of their service life in accordance with the currently applicable
legal requirements and guidelines.