Technical data
12.17 Position signaling switch
3VL molded-case circuit breakers
System Manual, 03/2009, 110 0110 - 02 DS 01
187
12.17 Position signaling switch
The position signaling switch of the SENTRON VL circuit breakers have the following technical data:
Table 12- 51 Position signaling switch
Technical data
Connection cross-sections
Screw-type terminal
Standard cross-sections (DIN 46228)
Tightening torques
Screws for cable connection
0.5 Nm
Rated operating temperature –40 °C to +85 °C
Data in accordance with IEC/EN 61058
Rated operating current I
e
with rated operating
voltage V
e
Standard operation
At V
e
250 V AC/400 V AC
I
e
16 A/10 A
Rated making capacity At 250 V AC
16 A
At 400 V AC
10 A
Rated thermal current I
th
16 A
Rated operating voltage 250 V AC 400 V AC
Rated breaking capacity
cosφ = 1 (resistive)
cosφ = 0.7 (inductive)
At 250 V AC
16 A
4 A
At 400 V AC
10 A
4 A
Short-circuit fuse (quick-response) At 250 V AC
16 A
At 400 V AC
10 A
Data according to UL 1054
Rated operating current I
e
with rated operating
voltage V
e
Alternating current
Standard operation
With V
e
, power,
[horsepower]
125/250 V AC, 1HP
I
e
16 A
Flammability
class
UL94V-0